Results
The Cool-phase system monitors and records temperatures, CO2 levels and energy use. The results below are based on data collected by the units installed in the room between 20th April 2012 and 24th June 2013.
Temperature Comparison
This table shows the overall average daily temperatures for the room. It is clear from the table that the Cool-phase systems have kept the temperature within a very comfortable band.
This table shows the percentage of time that the internal temperature has spent at over 25°C , 28°C and 32°C during the logged period.
The Cool-phase system has maintained an ideal temperature within the rooms of less than 25°C across the logged period for the majority of the time. With only a very small percentage of time being monitored at over 25°C and at no point exceeding 28°C, this more than meets the target for overheating in terms of either CIBSE guide A or BB101.
CO2 Levels
Background or atmospheric CO2 level is approximately 400 parts per million (ppm) and 1500 ppm or above would be considered a high level.
Energy Use
As shown in this table the two Cool-phase units installed in the Science Lecture Room used a combined 138.5 KWHs of energy across the logged period.
Assuming 0.11 £/KWh that amounts to £15.24 or an average of £0.25p a week.
Conclusion
The Monodraught Cool-phase system has shown that it meets the design criteria and specification that the client requested. A requirement for fresh air and to ensure that CO2 levels remain within acceptable boundaries, which the results above have proven is the case. The solution has also been shown to meet the overheating criteria, keeping temperatures within an acceptable level. This has been achieved with very low energy use and equally low running costs.