Control Instructions

 

Semi-automatic Windcatcher Controller

 
Positioner control panel showing LED display

Automatic control strategy programmed into controller
with manual damper override

Download installation instructions for Fully Automatic Windcatcher Controller

MODE OF OPERATION

Damper Overrides
Open Button – Opens the damper fully for a 20 minute period. After the 20 minutes the system reverts back to the automatic setting.

Close Button – Closes the damper fully for a 20 minute period. After the 20 minutes the system again reverts back to the automatic setting.

Automatic Settings

Temperature (°C)
Percentage Open (%)
0-17
0
17-18
10
18-19
15
19-20
25
Trickle Ventilation 10-25% damper open
20-24
35
24-25
60
25-26
80
>26
100
Manual overrides last for 1 hour

To return to auto setting press either 'OPEN' or 'CLOSED' button
when in override operation.

 